Product Details

Frequency
50 Hz Or 60 Hz
Rated Current
5 A To 100 A
Operating Temperature
-10°C To +50°C
Humidity Tolerance
Up To 95% Non-condensing
Type
Active Harmonic Filter

Input voltage: single phase 220V to 240V AC. Frequency: 50 Hz or 60 Hz. Harmonic compensation range: up to 50th harmonic order. Rated current: varies by model, typically from 5 A to 100 A. Control method: digital signal processor (DSP) based real-time harmonic detection and filtering. Response time: milliseconds to microseconds. Power factor correction capability: improves power factor close to unity. Protection features include overcurrent, short circuit, overvoltage, and thermal protection. Cooling is typically forced air or natural convection. Mounting options include wall-mounted or panel-mounted. Operating temperature ranges from -10°C to +50°C. Humidity tolerance is up to 95% non-condensing. Communication protocols such as Modbus or Profibus may be supported for monitoring and control. Compliance adheres to IEC standards and relevant industry norms

Yes! I am interested


Technical Specifications

Models p2p-415-apf3 p2p-415-apf4
Network Voltage 415Urms +10%/-15%
Connection 3P/4W 4P/4W
Grid Frequency 50Hz +/-5% (60Hz available on request)
Modularity Upto 32 units
Harmonic Filtering 2nd to 51st order
Individual Harmonic Selection Yes
Harmonic Attenuation >96%
Reactive Compensation Yes
Negative Sequence Compensation Yes Yes
Zero Sequence Compensation NA Yes
Compensation Open/Closed Loop
Reaction Time <100 micro seconds
Filter Consumption <3.0% of rated capacity (typical)
CT Specifications ratio based on peak load 0.5 class or better 15VA or more
Standards IEEE 519-1992 harmonic standards
USER INTERFACE
Interface 7" touch screen
Remote Interface Ethernet, MODBUS RTU
Configuration Settings Through User Interface and USB key
ENVIRONMENT
Protection Class IP41 (Higher on request)
Operating Temperature upto 45 degrees with adequate ventilation (upto 55 degrees with derating)
Operating Environment Indoor, Dust Free
Relative Humidity Maximum 95% (non condensing)
Altitude Upto 1000m